FIRE FIGHTING SYSTEMS

Arab Vision Safety is committed to providing the best fire protection solutions. One of our main services is the complete building firefighting
pipe networks to supply fire hose cabinet, sprinkler heads, etc. We also provide fire protection services such as underground firefighting piping networks to provide buildings and fire hydrants. The conventional fire piping system is associated with fittings, hangers, supports, and stationary/building based water pumps. Arab Vision Safety we provide clients with complete services of having this system installed including pump hydraulic calculations and engineering-related documentation.

Fire Sprinkler Systems (Wet Pipe):

A fire sprinkler system is an active fire protection measure, consisting of a water supply system, providing adequate pressure and flow rate to a water distribution piping system, onto which fire sprinklers are connected. Each closed-head sprinkler is held closed by either a heat-sensitive glass bulb or a two-part metal link held together with fusible alloy. The glass bulb or link applies pressure to a pip cap which acts as a plug which prevents water from flowing until the ambient temperature around the sprinkler reaches the design activation temperature of the individual sprinkler head. In a standard wet-pipe sprinkler system, each sprinkler activates independently when the predetermined heat level is reached.

At Arab Vision Safety we provide the fire sprinkler systems with a wide range of sprinkler head types for different applications, and to suit architects needs for aesthetic appearance. We are as well an official representative of Viking water network products and an authorized distributor and reseller. Wet pipe system uses automatic sprinklers attached to a piping system containing water and connected to a water supply so that the water discharges immediately from sprinklers operated by the heat from a fire. Wet pipe systems are typically used in accommodation and similar areas with solid combustibles. Wet pipe systems are the most common fire sprinkler system. A wet pipe system is one in which water is constantly maintained within the sprinkler piping. When a sprinkler activates this water is immediately discharged onto the fire.

Applications for Wet System

  •  Production Facilities
  •  Community Centers
  • Commercial Establishments
  • Residential Occupancies
  • Workshops / Garages
  • Schools / Colleges
  • Warehouses / Factories

A fire sprinkler system is an active fire protection method, consisting of a water supply system, providing adequate pressure and flow rate to a water distribution piping system, onto which fire sprinklers are connected. Although historically only used in factories and large commercial buildings, systems for homes and small buildings are now available at a cost-effective price Fire sprinkler systems are extensively used worldwide, with over 40 million sprinkler heads fitted each year. In buildings completely protected by fire sprinkler systems, over 96% of fires were controlled by fire sprinklers alone.

fire Hose Cabinets : –
– Fire hose cabinets are found indoors and outdoors. Indoors, the fire hose cabinets are connected to the building fire piping system at designed pressure. The fire hose cabinets are provided in a wide range of sizes, thickness, and finishes to comply with the local and international requirements and standards, and to fulfill architects and designers aesthetic appearance requirements . Other outdoor fire hose cabinets are used for different applications are also provided with different range of standards, thicknesses, sizes and finishes to suit the client and design requirements. The hose inside the cabinets are also provided in different materials such as rubber and synthetic fabrics, and in different settings such as hose reel and hose rack. Nozzles used to direct water to flames with a valve to control the water spread.

Fire Fighting Pumping Solutions:-
The fire protection industry has a wide range of fire pumps types and solutions. We at Arab
Vision Safety provide a wide range of fire pumping solutions from world-renowned
manufacturers such as Pentair, Aurora, Fairbanks Morse, Patterson and others.
Examples of these different solutions provided by Arab Vision Safety are:
* Horizontal Split-Case fire pumps .
* Horizontal split-case fire pumps .
* Vertical turbine fire pumps .
* End suction pumps .
* Jockey fire pumps .
* Complete pre-packed fire pump sets .

Horizontal Split-Case Fire Pumps:-
These types of pumps are ideal for low and high pressure requirements.
They are also able to be operated whether with electric motors, or diesel
engines.
We have provided the supply and installation services of UL/FM US-made horizontal split case fire pumps to different projects in the KSA.

Vertical Turbine Fire Pumps :-
These types of pumps provide flexibility staging that enables capacity in minimum floor spaces. No priming is necessary to provide flows from 500 gpm to 5,000 gpm (1,892 liters/min to 18,925 liters/min), with pressures in excess of 350 psi (24 bar). We have provided the supply and installation of UL/FM US-made vertical turbine fire pumps to different projects in the KSA

Fire Hydrant and FDC System :-
Fire hydrants and FDCs (Fire Department Connection) are systems installed outdoors and public areas and streets to support fire departments in the case of fire. The FDC is mainly a dry pipe network and in some projects are connected to buildings. Fire hydrant networks are wet pipes, and fed by stationary pumps for the purpose of fighting fire at public and outdoor areas. We at Home safety provide fire hydrants and FDC connections in accordance with the Saudi Civil Defense and international and NFPA standards to match with
 the Fire Departments connections and hoses.

Fire Pump Control and Check Valve
The BERMAD model 42T-20 is an elastomeric, hydraulically operated, self actuated Non Return Fire Pump Pressure Control Valve, designed for advanced fire protection systems meeting the NFPA-20 guidelines. The 42T-20 is used for controlling the flow and pressure at the pump discharge, performing also as a non return check valve.
The 42T-20 prevents pump startup surge, typically caused by the accelerated water flow during the fire pump starts. The valve also helps to prevent pump start negative suction pressure, preventing pump cavitation damage. Due to exceptional reliability, safe actuation and low head loss, the 42T-20 is highly suited for fire pump discharge pressure control applications.  As an option the 42T-20 can be fitted with a valve position indicator that can include a limit switch suitable for industrial monitoring systems.